Description
– Input type: J, K, T, N, R, S, B, E, Pt100, Pt1000, NTC and 0-50 mV
– Accuracy:
Typical:
Pt1000 / mV: 0.07 % of span
Pt100: 0.08 % of span
T/C: 0.07 % of span ±1 °C
NTC: 0.2 °C
– Maximum:
Pt1000 / mV: 0.15 % of span
Pt100: 0.15 % of span
T/C: 0.15 % of span ±1 °C
NTC: 0.45 °C
– Output type: 4-20 mA
– Output resolution: 0.25 µA
– Thermal drift: < 0.05 % / 25 °C
– Input-output isolation: 1.5 kVrms
– Electrical protection: reverse polarity
– HART® protocol version: HART V7, compatible with HART V5
– Configuration interface: via TxConfig-HRT adapter or HART® certified handheld
– Software: TxConfigII or certified HART® software
– Certifications and standards: CE, NAMUR NE43, RoHS, Reach, HART®
– Electromagnetic compatibility:
CISPR 11
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-8
– Operating conditions: -40 to 85 °C, 0 to 90% RH
– Power supply: powered by the 4-20 mA loop (10.5 – 35 Vdc)
– Dimensions: 114 mm x 99.5 mm
– Housing: ABS UL94-HB
– Format / mounting: 35 mm DIN rail