TEMP-WM and TEMP-DM Temperature Transmitter (Wall and Duct)

Quote on request

HVAC temperature transmitters

The TEMP-WM y TEMP-DM temperature transmitters include high-accuracy, highly stable sensors for temperature measurement. Measured values are converted into 4 to 20 mA output signals linearly related to the reading. Optionally, a 0 to 10 Vdc voltage output is available.
These microprocessor-based units can be fully configured using the TxConfig communication interface and the Windows® operating system.
The TEMP-WM model is intended for wall mounting, and the TEMP-DM model has an extended sensor sheath for duct or through-wall mounting.

SKU CL8979 Category

Description

– Pt100 sensor input: configurable
– Maximum measuring range: -200 to 650 °C
– Minimum measuring span: 40 °C
3-wire type, 0.20 mA excitation, a= 0.00385, per NBR 13773
To use a 2-wire Pt100, bridge terminals 2 and 3
– Total accuracy (ambient 25 °C): maximum error 0.2 % of full range for Pt100
– Response time: < 100 ms
– Output: 4-20 mA or 20-4 mA current, 2-wire; linear to the temperature measured by the sensor
– Output resolution: 0.004 mA (12 bits)
– Power supply: 12 to 35 Vdc, voltage across the transmitter
– Maximum load (RL): RL (max. in ohms) = (Vdc – 12) / 0.02
– Where: Vdc = supply voltage in volts (12 to 35 Vdc)
– Operating temperature: -40 to 50 °C
– Ambient humidity: 0 to 90 % RH
– Calibration thermal drift: ± 40 ppm of full range per °C
– Electromagnetic compatibility: EN 50081-2, EN 50082-2
No electrical isolation between input and output
Internal protection against reverse supply voltage polarity
– ABS housing, 34 mm diameter and maximum height of 18 mm

Additional information

Output

4-20 mA

Mounting

Wall or duct