DigiRail Connect Ethernet I/O Module

Quote on request

DigiRail Connect is a versatile I/O module that can be used as an extension in automation systems of any brand. Its varied, combined inputs and outputs provide analog and digital signals for reading or transmission in industrial standards. The many DigiRail Connect options available ensure the best choice for the customer’s application.

Bringing Industry 4.0 to the DIN rail, the connectivity of DigiRail Connect lets it be used as a Modbus RTU slave device on RS485 networks or as a Modbus TCP server device on an Ethernet network.

Designed especially for harsh environments, DigiRail Connect meets the strictest EMC and EMI standards, providing robustness and reliability for industrial applications.

Description

– Inputs:
RAMIX: 4 digital and 2 analog (isolated)
DMIX: 8 digital
– Outputs:
RAMIX: 3 digital or 2 relays and 2 analog (isolated)
DMIX: 4 relays or 8 digital
– Analog input types:
J, K, T, N, E, R, S and B thermocouples
Pt100, Pt1000, NTC,
0-60 mV, 0-5 V, 0-10 V, 0-20 mA, 4-20 mA
– Analog input impedance:
0-60 mV, Pt100, Pt1000, NTC and thermocouples: >10 MΩ
0-5 V, 0-10 V: >1 MΩ
4-20 mA: 15 Ω + (1 V @ 20 mA)
– Digital input characteristics:
Logic level “0”: < 0.5 V; logic level “1”: > 3 V
Maximum voltage: 30 V
Input impedance: 270 kΩ
Input current: @ 30 Vdc (typical) 0.15 mA
Maximum frequency (square wave)
Dry contact: 10 Hz
PNP: 250 Hz
NPN: 250 kHz
– Digital output characteristics:
Maximum load current: 500 mA
Short-circuit current: 200 mA
Maximum switching voltage: 30 Vdc
Minimum switching voltage: 6 Vdc
– Relay output characteristics:
Type: SPST-NO and SPDT
Maximum load current: 3 A (SPST) / 6 A (SPDT)
Switching voltage: 250 Vac
Suitable for resistive loads
– Analog output characteristics:
Signal types: 0-20 mA, 4-20 mA, 0-10 V
Maximum load: 0-20 / 4-20 mA: ≤ 500 Ω
0-10 V: ≥ 2000 Ω
– Analog channel resolution:
Analog inputs: 16 bits (65000 levels)
Analog outputs: 12 bits
– Communication interface:
USB
Ethernet: 10/100 Mb/s, IEEE 802.3u standard
RS485
– Software:
NXperience (via USB)
– Power supply:
Voltage: 10 Vcc a 36 Vcc
Maximum consumption: 5 W
Typical consumption: 20 mA
– Operating conditions:
Temperature: -20 to 60 °C (-4 to 140 °F)
Humidity: 5 to 95% RH, non-condensing
– Enclosure:
ABS+PC

Additional information

Type

I/O module and PLC